Pathfinder variable trip test point faulted circuit indicators fci which quickly and easily locate faulted sections of underground cable systems.
Underground cable fault indicators.
The utility can easily identify the faulted cable section without a time consuming re fuse.
Nearby capacitor banks on the overhead system can make outrush worse.
Fault indicators can be installed on transformers switchgear sectionalizing cabinets bushing terminators overhead lines and underground cable.
This catalog describes features and ordering information for eaton s cooper power series s t a r.
Underground faulted circuit indicators specifications trip point 50 a 5 100 a 1 200 a 2 300 a 3 400 a 4 450 a 4 5 500 a 5 600 a 6 800 a 8.
If a fault causes a feeder fuse to operate the indicators upstream of the fault trip and the indicators after the fault remain untripped.
The quantity and location of the fault indicators should be sufficient to eliminate the need for the sectionalizing fault chasing method.
Underground fault indicators are placed on each primary cable.
Faulted circuit indicators are attached to underground cable accessories such as 200 a and 600 a elbows and indicate the passage of fault current by showing an orange reflective target in its fisheye display.
Elastimold underground cable accessories.
Sel designs and manufactures fault indicators and sensors supplying utilities around the world with products that help reduce fault finding time so that power can be restored quickly after a fault occurs.
Some units will give separate indication for short cir.
Sel underground autoranger fault indicators are reliable self adjusting settings free faulted circuit indicators suitable for applications with fault current ranging from 50 a to greater than 1 200 a.
Mcnulty 1994 reported that 2000 ft of 15 kv cable created an oscillatory current transient that peaked at 100 a and decayed in 0 15 msec.
The cabletroll indicators are fault current detectors for the underground medium voltage distri bution network 6 36kv.
Overview of fault indicators.
Faulted circuit indicators can also be installed on cable terminations connected to pad mounted distribution transformers and switchgear.
Line fault indicators consist of a solid state current sensor connected to a faulted circuit display.
Cabletroll 2300 series fault indicators is a complete system for indication of phase to ground and phase to phase faults in underground 6 36 kv mv cable networks with multi core cables where sensors can be mounted in a safe area on the cable termination.
Downstream of a fault the stored charge in the cable will rush into the fault possibly tripping fault indicators.